Engineered Dehumidifiers
NSI 5000D , NSI 6000D, NSI 10000D, NSI 20000D
Dedicated desiccant air-supply units provide lowhumidity discharge conditions necessary to maintain a dry environment. It's a simple solution to an old problem. The solid desiccant rotor absorbs moisture from process air. The moisture is taken out of the rotor by a second and separate reactivating airstream. This process enables the rotor to continually take moisture out of the airstream without interruption.
NSi Series units provide an excellent stand-alone solution when sensible heat gain is not a concern. To solve existing moisture problems NSi Series units can be added to existing conventional HVAC systems. The fully integrated dehumidifi er is complete with process and reactivation fi lters, fans and the complete control system for safe operation. Choose between direct gas fi red, steam, or electric actively heated reactivation.
TECHNICAL FEATURES | |
---|---|
Single Frame Compact Design | |
GI/SS material with Corrosion Resistance coating | |
Energy-efficient controls | |
In build RH & Temp Monitering System | |
Adjustable Performance with VFD | |
Easy Installation & Maintenance | |
Fully Dismantle for Remote Location | |
Steam/ Gas reactivation available | |
Mfg With Swedish Technology |
Product Specification : | NSI 5000 ED | NSI 6000 ED | NSI 8000 ED | NSI 10000 ED | NSI 15000 ED | NSI 20000 ED |
---|---|---|---|---|---|---|
Nominal Capacity1 (Kg/Hr) |
37.5 |
45 |
60 |
75 |
112.5 |
150 |
AHU Air Flow M3/Hr CFM |
5000 3000 |
6000 3500 |
8000 5000 |
10000 6000 |
15000 9000 |
20000 12000 |
Static Pressure Pa |
1470 |
1470 |
1470 |
1470 |
1470 |
1470 |
Process air-DH Unit Nominal air flow (m3/h) |
5000 |
6000 |
8000 |
10000 |
15000 |
20000 |
Reactivation air Nominal air flow (m3/h) Static pressure (Pascal) |
1650 500 |
2000 500 |
2000 500 |
2000 500 |
2000 500 |
2000 500 |
Moisture Balance | 1.0089 | |||||
Temp Balance | 0.94978 | |||||
Efficiency(Kwh/KgH20) | 1.34 | |||||
Heater power (kW) | 45 | 54 | 72 | 90 | 135 | 180 |
Total power (kW) | 49.7 | 58.7 | 81 | 99 | 148.2 | 198.7 |
1. Valid for inlet conditions 20°C/60%RH.
2. Steam Option -Available.
3. Chilled Water/Dx Coil -Available.
DOWNLOAD | |
---|---|
click here to download pdf |